Tancy TDF-II Differential Pressure Flow Meter User Manual

TDF-II differential pressure flow meter adopts digital sensor, low power consumption and other technologies to develop a new generation of differential pressure flow meter with local flow, pressure, differential pressure and temperature display, which is used for natural gas flow measurement. It can be equipped with throttling elements (standard orifice/Venturi tube/wedge orifice), temperature sensor, pressure sensor, differential pressure sensor, differential pressure flow accumulation meter according to user's needs. It can be widely used in oil and gas field natural gas production and petroleum, chemical, power, metallurgy and other industries natural gas flow measurement.


Tancy TDF-II Differential Pressure Flow Meter User Manual - cover page
Brand
Tancy
Category
Other products
Document type
User Manual
Language
Chinese
Pages
8
File format
PDF
File size
1.9 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
392166842933631A2087584481616862

About this manual

Tancy TDF-II is a differential pressure flow meter developed with digital sensors and micro-power technology for natural gas flow measurement. It combines a throttling element (standard orifice plate, Venturi tube, or wedge plate), temperature, pressure, and differential pressure sensors, and a differential pressure flow computer, with local display of flow, pressure, differential pressure, and temperature. It complies with GB/T 21446, JJG 640, and Q/TX 64.

The manual describes its features, working principle and structure, technical parameters, electrical installation, display, settings, installation precautions, packaging, unpacking, and ordering information. Features include a 15:1 range ratio, two years of daily history records, low power consumption with an internal lithium battery lasting two years or more, password-protected parameters, and outputs such as frequency pulse, 4-20 mA, RS485, and HART. This manual is written in Chinese.

What's inside

  • Overview
  • Main features
  • Working principle and structure
  • Main technical parameters
  • Electrical installation
  • Display
  • Settings
  • Installation and use precautions
  • Packaging, transport and storage
  • Unpacking and inspection

Specifications

Differential pressure range40 kPa
Nominal pressure1.6, 2.5, 2.0, 4.0, 5.0, 6.3, 10.0 MPa
Maximum working pressure6.3 MPa
Measurable temperature and medium-20 to +80 C; natural gas, air
Accuracy note10:1 range ratio accuracy class 1.5; 15:1 range ratio accuracy class 2.5; class 5 for natural gas wellhead measurement
Range ratioUp to 15:1
History recordsTwo years of daily records
External power(8-24) V DC
Internal power3.6 V lithium battery, usable for two years
Ambient temperature-30 to +70 C
Relative humidity5-95%
Atmospheric pressure86-106 kPa
Explosion-proof markEx d II B T4 Gb
Protection ratingIP65
Communication capacityRS485, up to 32 flow meters per host
4-20 mA outputOutput accuracy ±0.3%FS; transmission distance ≤300 m
Frequency output1000 Hz proportional to full-scale flow
Pulse output unit0.001, 0.01, 0.1, or 1 per unit flow
RS485 distance≤1200 m
HART distance≤1500 m
Sensor diaphragm material316SS
Clamping flange material304SS
Nominal diametersDN40, DN50, DN80, DN100, DN150, DN200

Frequently asked questions

What standards does the TDF-II flow meter comply with?

It complies with GB/T 21446, JJG 640, and Q/TX 64.

What is the differential pressure range?

The differential pressure range is 40 kPa.

How long can the internal battery operate?

The internal 3.6 V lithium battery can operate for two years.

How many flow meters can one host connect over RS485?

Each host can connect up to 32 flow meters.