This file introduces the basic knowledge of lead-acid batteries, including the development history and status quo of lead-acid batteries, the definition, classification, basic principle, performance parameters, self-discharge, basic structure, design, charging and discharging characteristics, capacity factors, failure modes, use and maintenance, etc.
This 34-page training manual was published by Beijing Tianyi Xinke Technology Co., Ltd. in December 2007. It presents lead-acid battery knowledge, with emphasis on valve-regulated lead-acid (VRLA) batteries, for technical training and use guidance.
The document covers the history and current status of lead-acid batteries, the definition and AGM/GEL classification of VRLA batteries, their electrochemical principle and oxygen cycle, performance parameters, self-discharge, basic structure and design. Later sections discuss charge and discharge characteristics, capacity factors, failure modes, installation and charging, recommended operating conditions, maintenance, and parameter settings. This manual is written in Chinese.
| AGM oxygen recombination efficiency | 99% or more in lean-electrolyte condition |
|---|---|
| GEL oxygen recombination efficiency | 70–90% in dry/cracked condition |
| Flooded battery sealing reaction efficiency | nearly zero |
| Oxygen evolution at positive plate during charging | starts at 70% charge |
| Hydrogen evolution at negative plate during charging | starts at 90% charge |
VRLA stands for Valve Regulated Lead Battery.
They are AGM and GEL (colloidal) batteries.
Hydrogen evolution is suppressed and water loss is very small, so acid and water do not need to be added during use.
It is the terminal voltage of the battery in the open-circuit state, equal to the difference between the positive and negative electrode potentials.