DDS33 single phase multi-function power meter instruction manual, including purpose, scope of application, specification, technical parameters, installation and use, etc.
The DDS33 is a single-phase multi-function electronic power meter in a DIN-rail case with RS485 communication, described in this Chinese instruction manual (document number PA 2018E472-33). The manual states its purpose and scope, main specifications and technical parameters, installation and use, wiring and outline diagrams, test method, transport and storage, and the warranty period.
According to the text, the meter is made in accuracy class 1 or 2 at a rated voltage of 220 V, with rated currents from 1.5(6) A up to 30(100) A, a 7-digit LCD showing total energy, voltage, current and power, and a communication protocol that follows DL/T645-2007 so data can be read over RS485 or by an infrared reader. It is intended for fixed indoor installation on a 35 mm DIN rail. This manual is written in Chinese.
| Accuracy class | Class 1 or class 2 |
|---|---|
| Rated voltage (Ub) | 220 V |
| Rated current ranges | 1.5(6)A, 5(20)A, 5(30)A, 10(40)A, 15(60)A, 20(80)A, 20(100)A, 30(100)A |
| Rated frequency | 50 Hz or 60 Hz |
| Display | 7-digit LCD showing total energy, voltage, current, power, communication address |
| Communication | RS485 or infrared reader, DL/T645-2007 protocol |
| Mounting | 35 mm DIN rail |
| Operating ambient temperature | -25 °C to +55 °C |
| Storage ambient temperature | -35 °C to +65 °C |
| Insulation | 6 kV 1.2/50 µs impulse voltage; 2 kV AC 50 Hz for 1 minute |
| Pulse test output | Optocoupler output; +5 VDC to terminal 4 (positive), signal S to terminal 3 (negative) |
| Warranty | 18 months from the date of manufacture |
The rated voltage is 220 V. Rated current depends on the version, with ranges from 1.5(6) A to 30(100) A, where the value in brackets is the maximum current Imax.
It is installed indoors in a ventilated, dry place on a 35 mm DIN rail, with the base plate fixed to a firm, fire-resistant and vibration-free wall.
Communication follows the DL/T645-2007 protocol, and total energy, voltage, current and power can be read over RS485 or with an infrared handheld reader.
The manufacturer repairs or replaces the meter free of charge if a quality problem appears within 18 months from the date of manufacture, provided the lead seal is intact and the transport, storage, installation and use rules were followed.