Describes how to install a Generator Connection Cabinet with a key interlock provision
This document from Berthold Electric describes Option 2, a provision only for a key interlock on the Generator Connection Cabinet. The interlock itself is not provided and must be supplied by the end user or installing contractor, because key interlocks must be purchased with matching keys. The provisions are designed to accept interlocks made by the Kirk Key Interlock Company.
The sheet lists the Kirk Key interlock model numbers to order for wall mount units with Cam-Loks and all pad mount units, and for wall mount units without Cam-Loks (mechanical lugs for generator connection). It then gives mounting details for the main body, latching block and chain, including the bolt sizes to use.
| Interlock model for wall mount units with Cam-Loks and all pad mount units | Kirk Key Interlock model # KDL0---10 (no bolt extension) |
|---|---|
| Interlock model for wall mount units without Cam-Loks | Kirk Key Interlock model # KDM0---10 (no bolt extension) |
| Accepted interlock manufacturer | Kirk Key Interlock Company (SD Series) |
| Main body mounting bolts, Cam-Lok and pad mount units | 3/8-16 x 2 in. long bolts |
| Latching block mounting hardware | 3/8-16 x 2 1/2 in. long bolts and nuts |
| Main body mounting bolts, units without Cam-Loks | 3/8-16 x 2 in. long bolts on exterior of main front door |
| Chain fastening bolt | 3/8-16 x 3/4 in. long (or longer) bolt through any link inside the door |
No. Option 2 is a provision only; the interlock itself is not provided and must be supplied by the end user or installing contractor.
Kirk Key Interlock model # KDL0---10, where the dashes indicate no bolt extension.
Kirk Key Interlock model # KDM0---10, used on units with mechanical lugs for generator connection.
They are designed to accept interlocks made by the Kirk Key Interlock Company.