Ximandun ZAC29C Multifunction Three-phase Power Regulator User Manual

This manual provides a detailed introduction to the model definition, product series, main technical indicators, input, output, LED indicator definition, wiring and application, preliminary debugging and troubleshooting of the ZAC29C series products


Ximandun ZAC29C Multifunction Three-phase Power Regulator User Manual - cover page
Brand
希曼顿
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
5
File format
PDF
File size
698 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
9B29231158D454CF04CAE392D81E403E

About this manual

The ZAC29C is a multifunction three-phase power regulator from Ximandun. It accepts a manual DC 0–5 V setting signal and automatic 4–20 mA or 2 s PWM input, and provides PWM or CYC output with power-control mode. The document covers model definitions, the product series, main technical specifications, LED indicator definitions, wiring and applications, basic and standard wiring diagrams, preliminary debugging and troubleshooting, and dimension drawings.

It is intended for pure resistive loads with three-phase full control or two-phase control and uses internal SSRs. Features described include external start/stop and manual/automatic contacts, fan-stop detection, over-temperature protection above 80 °C, and AL1/AL2 relay alarm outputs. This manual is written in Chinese.

What's inside

  • 型号定义
  • 产品系列
  • 主要技术指标
  • LED 指示灯定义
  • 配线及应用
  • 基本运行接线图
  • 标准接线图
  • PWM 输入,光电隔离的功率扩展技术
  • 初步调试和故障排除
  • 尺寸图

Specifications

Manual setpoint inputDC 0–5 V
Automatic control signal4–20 mA, input impedance < 250 Ω
PWM input2 s period, maximum input current < 5 mA
Fan power supply220 VAC, 50 Hz
Output resolution0.2
Output and control modesPWM or CYC output; power-control mode
Alarm outputRelay contacts AL1 and AL2, 240 VAC 2 A
LoadThree-phase full control or two-phase control pure resistive load, no phase sequence
Internal supply380 V
Over-temperature protectionOutput disabled and alarm when heatsink temperature is above 80 °C
Operating temperature-10 °C to +55 °C
Operating humidity≤90%

Frequently asked questions

How do I switch to PWM input?

Open jumper positions 1–2 on the internal MS shorting point; the input then becomes a 2 s PWM signal. Set the instrument or PLC output period to 2 s.

How do I change the output mode to PWM?

Short terminals P/C; the output mode becomes PWM.

What does a flashing red fault lamp indicate?

It indicates that the CS fan has stopped.

What should I use as a dummy load for preliminary testing?

Use a 100–200 W lamp as the dummy load, set the instrument to manual mode, and check that the load voltage switches within the switch voltage range.