Pentair Equipment Protection 89115007 Rev. G P/N 89115008 Hazardous Location Heaters 400W and 600W Models INSTRUCTION MANUAL Product Manual

This is the product manual for Pentair Equipment Protection 89115007 Rev. G P/N 89115008 Hazardous Location Heaters 400W and 600W Models INSTRUCTION MANUAL, which mainly introduces the application scenarios, technical data, design data, explosion protection, installation instructions, minimum clearances, operation, wiring diagram, maintenance, safety instructions, CE declaration, warranty, return and repair policy, and limitation of liability.


Pentair Equipment Protection 89115007 Rev. G P/N 89115008 Hazardous Location Heaters 400W and 600W Models INSTRUCTION MANUAL Product Manual - cover page
Brand
Pentair Equipment Protection
Category
Heater
Document type
User Manual
Language
English
Pages
12
File format
PDF
File size
989 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
A929B5CEC4A2EA66459393EA346F6CD2

About this manual

This instruction manual from Pentair Equipment Protection (document 89115007 Rev. G, P/N 89115008) covers the CP MEGATHERM hazardous location heaters in 400 W and 600 W versions, models DAHHL400XA and DAHHL600XA. The electric-finned heaters are designed for heating small enclosures or cabinets that hold measuring instruments, control valves or similar equipment in hazardous areas, and are recommended where a heating block cannot be mounted directly to a flat surface.

The manual gives application notes, technical and design data, explosion protection details and certificates, installation instructions with minimum clearances, operation, a wiring diagram, maintenance and safety instructions, plus a CE Declaration of Conformity, warranty and return and repair policy. It notes that the heaters must be installed with a thermostat to avoid damage, and that thermostat models HLTSTAT10C and HLTSTAT20C are sold separately.

What's inside

  • Application
  • Technical Data
  • Design Data
  • Explosion Protection
  • Installation Instructions
  • Minimum Clearances
  • Operation
  • Wiring Diagram
  • Maintenance
  • Safety Instructions

Specifications

ModelsDAHHL400XA (400 W), DAHHL600XA (600 W)
Rated voltage120 VAC (108-132 range) or 230 VAC (207-253 range)
Nominal power400 W / 600 W
Temperature classT3
Ambient temperature-76 to +140 F (-60 to +60 C)
Maximum operating temperature range-76 to +302 F (-60 to +150 C)
Ingress protectionIP66 / IP68 (1 bar / 30 min)
MaterialSeawater-proof aluminium, black anodized
Connection cable39 in. (1 m) silicone cable, notch and oil resistant, 3x AWG16, Ø 0.37 in. (9.4 mm)
Conduit connection½ NPT
Dimensions400 W: 8.9 x 9.0 x 2.4 in. (225 x 229 x 60 mm); 600 W: 12.8 x 9.0 x 2.4 in. (325 x 229 x 60 mm)
Weight400 W: 7.9 lb (3600 g); 600 W: 11.7 lb (5300 g)
Installation positionFins vertical

Frequently asked questions

What is the ingress protection rating of the heater?

The heater is rated IP66 / IP68 (1 bar / 30 min).

Does the heater require maintenance?

No. The manual states that the heater requires no maintenance, though performance and safety tests can be conducted at intervals set by the operator.

Must the heater be installed with a thermostat?

Yes. CP heaters must be installed with a thermostat to avoid damage to the heater; thermostat models HLTSTAT10C and HLTSTAT20C are sold separately.

What is the maximum temperature with T3 heaters?

The maximum is 160 C (320 F) with T3 heaters.

Download PDF (989 KB)