This is the product manual for Pentair Equipment Protection 89115007 Rev. G P/N 89115008 Hazardous Location Heaters 400W and 600W Models INSTRUCTION MANUAL, which mainly introduces the application scenarios, technical data, design data, explosion protection, installation instructions, minimum clearances, operation, wiring diagram, maintenance, safety instructions, CE declaration, warranty, return and repair policy, and limitation of liability.
This instruction manual from Pentair Equipment Protection (document 89115007 Rev. G, P/N 89115008) covers the CP MEGATHERM hazardous location heaters in 400 W and 600 W versions, models DAHHL400XA and DAHHL600XA. The electric-finned heaters are designed for heating small enclosures or cabinets that hold measuring instruments, control valves or similar equipment in hazardous areas, and are recommended where a heating block cannot be mounted directly to a flat surface.
The manual gives application notes, technical and design data, explosion protection details and certificates, installation instructions with minimum clearances, operation, a wiring diagram, maintenance and safety instructions, plus a CE Declaration of Conformity, warranty and return and repair policy. It notes that the heaters must be installed with a thermostat to avoid damage, and that thermostat models HLTSTAT10C and HLTSTAT20C are sold separately.
| Models | DAHHL400XA (400 W), DAHHL600XA (600 W) |
|---|---|
| Rated voltage | 120 VAC (108-132 range) or 230 VAC (207-253 range) |
| Nominal power | 400 W / 600 W |
| Temperature class | T3 |
| Ambient temperature | -76 to +140 F (-60 to +60 C) |
| Maximum operating temperature range | -76 to +302 F (-60 to +150 C) |
| Ingress protection | IP66 / IP68 (1 bar / 30 min) |
| Material | Seawater-proof aluminium, black anodized |
| Connection cable | 39 in. (1 m) silicone cable, notch and oil resistant, 3x AWG16, Ø 0.37 in. (9.4 mm) |
| Conduit connection | ½ NPT |
| Dimensions | 400 W: 8.9 x 9.0 x 2.4 in. (225 x 229 x 60 mm); 600 W: 12.8 x 9.0 x 2.4 in. (325 x 229 x 60 mm) |
| Weight | 400 W: 7.9 lb (3600 g); 600 W: 11.7 lb (5300 g) |
| Installation position | Fins vertical |
The heater is rated IP66 / IP68 (1 bar / 30 min).
No. The manual states that the heater requires no maintenance, though performance and safety tests can be conducted at intervals set by the operator.
Yes. CP heaters must be installed with a thermostat to avoid damage to the heater; thermostat models HLTSTAT10C and HLTSTAT20C are sold separately.
The maximum is 160 C (320 F) with T3 heaters.