The XMB7000/XMG7000 series of dual-loop digital instruments have 2 analog input channels, 2 analog output channels, and 4 switch output channels. It is suitable for measuring, displaying, controlling and outputing industrial process parameters such as temperature, pressure, liquid level and flow.
The XMB7000 and XMG7000 series are dual-loop digital instruments with two analog inputs, two analog outputs and four digital outputs, used to measure, display, control and transmit process parameters such as temperature, pressure, liquid level and flow. The manual covers features and technical parameters, input type (index number) selection, installation and wiring, display description, operation overview, detailed parameter setting and common faults with accessories.
Inputs are universal and are selected by hardware links and parameter settings: RTDs such as Pt100 and Cu50, thermocouples K, E, S, B, J, R, N and T, and standard signals 0-10 mA, 4-20 mA, 0-5 V and 1-5 V. The XMB7000 has dual digital displays, while the XMG7000 has dual digital displays plus light bars. Each loop has its own upper/lower limit alarm control output and a 0-10 mA, 4-20 mA, 0-5 V or 1-5 V transmitter output, and an isolated RS485 interface is optional. Power is AC 90-265 V (50-60 Hz) or DC 24 V. This manual is written in Chinese.
| Power supply | AC 90-265 V (50-60 Hz) or DC 24 V |
|---|---|
| Operating ambient temperature and humidity | 0 to 50 °C; relative humidity below 90% |
| Power consumption and weight | Less than 3 W; less than 0.5 kg |
| Thermocouple input impedance | Greater than 10 MΩ |
| Voltage input impedance | Greater than 300 kΩ |
| Current input impedance | 250 Ω |
| Display resolution | 0.001, 0.01, 0.1, 1 |
| Transmitter output load | Current output below 600 Ω; voltage output 200 kΩ or more |
| Transmitter supply output | 24 V DC ±10%, maximum 100 mA |
| Relay contact capacity | 3 A 220 V AC or 3 A 24 V DC, resistive load |
| Dimensions | 160 × 80 × 150 mm or 80 × 160 × 150 mm |
They use a universal input that can be set for RTDs such as Pt100 and Cu50, several thermocouple types, and standard signals 0-10 mA, 4-20 mA, 0-5 V and 1-5 V.
The XMB7000 has dual digital displays, while the XMG7000 adds dual light-bar display alongside the digital display.
Each loop has its own upper and lower limit alarm control output and a 0-10 mA, 4-20 mA, 0-5 V or 1-5 V transmitter output.
An isolated RS485 communication interface can be supplied.