Jinheng JZH-A Series Constant Current Energy-Saving Phase Advancer Technical Specifications

This document is the technical specifications of the JZH-A series constant current energy-saving phase advancer, which introduces the characteristics and features of the product.


Jinheng JZH-A Series Constant Current Energy-Saving Phase Advancer Technical Specifications - cover page
Brand
Jinheng
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
15
File format
PDF
File size
201 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
150544B7EA592FF1F49601B3BBB1B350

About this manual

Jinheng JZH-A series constant current energy-saving phase advancers are local reactive-power compensation devices connected in the rotor circuit of large wound-rotor asynchronous motors. They are intended to improve power factor and efficiency and reduce energy loss.

The document covers the operating principle, model designation, technical parameters and installation conditions, wiring, dimensions, operation, maintenance, troubleshooting, transport, unpacking, ordering and quality assurance. Stated parameters include power factor above 0.95, reactive power reduction above 60%, stator current reduction of 10%-20%, three-phase 380 V±10% 35 A 50 Hz supply, IP20/IP30 protection and ambient limits. This manual is written in Chinese.

What's inside

  • Overview
  • Working principle
  • Model designation
  • Main technical parameters and operating environment
  • Wiring and precautions
  • Product specifications and installation dimensions
  • Operation method
  • Basic maintenance
  • Troubleshooting guide
  • Transport and storage

Specifications

Power factor after compensationAbove 0.95
Reactive power reductionMore than 60%
Stator current reduction10% to 20%
AltitudeNot higher than 1000 m
Ambient temperatureNot higher than 40°C
Relative humidityNot higher than 90%
Power supplyThree-phase AC 380 V ±10%, 35 A, 50 Hz
Protection gradeIP20/IP30
Cabinet height2000 mm

Frequently asked questions

What is the JZH-A series phase advancer used for?

It is a local reactive-power compensation device connected in the rotor circuit of large wound-rotor asynchronous motors to improve power factor and efficiency and reduce energy loss.

What power factor can be achieved after compensation?

The motor power factor can be raised to above 0.95.

What power supply is required?

A three-phase AC supply of 380 V ±10%, 35 A, 50 Hz is required.

What installation environment is required?

The altitude should not be higher than 1000 m, temperature not higher than 40°C, relative humidity not higher than 90%, and the location should have no dangerous, explosive or corrosive gases.