This document introduces the installation, use and maintenance of ICT 1000 & RFM series network products.
This manual describes the RFM 1 & 4 units, which provide termination points for the ICT transmitter and connections for power and digital signal cabling, with pass-through connections for simple multi-drop network creation. When partnered with PSM's RFM-ISR units, the network can also provide intrinsic safety compliance.
It covers network installation principles for RS485 Modbus RTU networks, including unique Modbus IDs, power supply sizing, cable length and conductor requirements, termination resistors, electromagnetic compatibility earthing, intrinsically safe installation requirements, and typical network configurations.
| Network protocol | Modbus RTU |
|---|---|
| Maximum ICT current consumption | 23 mA |
| ICT current consumption in digital-only mode | 4 mA maximum |
| Maximum total communications cable length | 1200 metres |
| Minimum conductor size | 0.5 mm |
| Termination resistor value | 120 ohm |
| RFM-ISR barrier maximum current rating | 315 mA |
| Maximum number of ICTs on one network | 127 |
The network protocol is Modbus RTU.
An ICT has a maximum current consumption of 23 mA.
The total communications loop cabling should not exceed 1200 metres.
120 ohm termination resistors are used.