This manual describes the RFM 1 & 4 units, which provide termination points for the ICT transmitter and connections for power and digital signal cabling, with pass-through connections for simple multi-drop network creation. When partnered with PSM's RFM-ISR units, the network can also provide intrinsic safety compliance.

It covers network installation principles for RS485 Modbus RTU networks, including unique Modbus IDs, power supply sizing, cable length and conductor requirements, termination resistors, electromagnetic compatibility earthing, intrinsically safe installation requirements, and typical network configurations.

What's inside

  • Network Installation
  • Network Operation
  • Modbus ID
  • Power Supply
  • Network Cabling
  • Termination Resistors
  • Electromagnetic Compatibility
  • Intrinsically Safe Installations
  • Typical network configurations
  • Certification

Specifications

Network protocolModbus RTU
Maximum ICT current consumption23 mA
ICT current consumption in digital-only mode4 mA maximum
Maximum total communications cable length1200 metres
Minimum conductor size0.5 mm
Termination resistor value120 ohm
RFM-ISR barrier maximum current rating315 mA
Maximum number of ICTs on one network127

Frequently asked questions

What network protocol does the network use?

The network protocol is Modbus RTU.

What is the maximum current consumption of an ICT?

An ICT has a maximum current consumption of 23 mA.

What is the maximum recommended total communications cable length?

The total communications loop cabling should not exceed 1200 metres.

What value of termination resistor is used?

120 ohm termination resistors are used.