ZSR-WE-2184S is a remote analog/digital signal acquisition and remote relay control terminal device (RTU) using WiFi network and Ethernet. It is equipped with industrial-grade WiFi/Ethernet modules and embedded processors, which realizes the integration of field data acquisition/wired transmission, wireless transmission/remote control, and offers a cost-effective solution.
The ZSR-WE-2184S from Chengdu Zhongshan Technology is a telemetry terminal (RTU) that uses WiFi and Ethernet networks for remote analog and digital data acquisition and remote relay control. It has a built-in industrial WiFi/Ethernet module and embedded processor, and provides 8 analog inputs (0-20mA/0-5V/0-10V/0-30V selectable), 4 optocoupler-isolated digital inputs, 4 independent relay outputs, one RS232 port for parameter configuration and one RS485 port using Modbus RTU.
The manual (version V1.2, dated September 8, 2021) describes the hardware interfaces, terminal definitions, LED indicators, analog range jumper settings and technical parameters. It also covers software functions such as transparent transmission, TCP/UDP/MQTT/HTTP protocols, Modbus RTU to Modbus TCP conversion, the vendor's cloud service, MQTT communication testing and the RTU's script function for automatic data collection. This manual is written in Chinese.
| Power Supply | Standard 12VDC/1A, voltage range 6-30VDC |
|---|---|
| Idle Power Consumption | 8mA at 12VDC |
| Data Transmission Consumption | 80mA-340mA at 12VDC |
| Analog Inputs | 8 channels, 0-20mA/0-5V/0-10V/0-30V selectable |
| Digital Inputs | 4 optocoupler-isolated channels |
| Relay Outputs | 4 independent channels, max load 250VAC/30VDC@3A |
| Serial Interfaces | RS232 and RS485, 1200bps-115200bps, data bits 8, parity N/E/O, stop bits 1/2 |
| Antenna Connector | 50Ω SMA |
| WiFi | IEEE 802.11b/g/n, 2412-2484 MHz |
| Ethernet | 10M/100M auto-negotiation |
| Temperature Range | -40℃ to +85℃ |
| Dimensions | 145mm x 90mm x 40mm |
| Weight | 210g |
The standard supply is 12VDC/1A with an accepted voltage range of 6-30VDC; the recommended adapter is the one supplied with the product.
It provides 8 analog inputs (0-20mA/0-5V/0-10V/0-30V selectable), 4 optocoupler-isolated digital inputs and 4 independent relay outputs.
A 1-second blink means the device is connecting to the network, two fast blinks every 4 seconds means it is connected to WiFi/Ethernet and establishing a connection to the data center, and a blink every 5 seconds means the data center connection is established.
No. Only communication parameters can be modified remotely; interface parameters can only be changed through the local serial port.