Maple Armor FW109 Fire Alarm Controller (Linkage Type) Installation and Operation Manual

The FW109 fire alarm controller (distributed type) is a smart fire alarm device that supports 99 controllers networking, and each controller supports 16 loops (200 points of on-site components/loops).


Maple Armor FW109 Fire Alarm Controller (Linkage Type) Installation and Operation Manual - cover page
Brand
Maple Armor
Category
Other
Document type
User Manual
Language
Chinese
Pages
24
File format
PDF
File size
1.4 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
E0851C215437EF5DD8111E7A1BCF2112

About this manual

The FW109 is a linkage-type fire alarm controller from Maple Armor for small and medium-sized sites. It meets GB 4717-2005, supports 16 loops per controller with up to 200 field devices per loop, and allows up to 99 controllers to be networked.

The installation and operation manual covers features, specifications, main functions, installation and commissioning, battery connection, on-site commissioning, the operating interface, printer paper use, and common fault analysis and maintenance. This manual is written in Chinese.

What's inside

  • Features
  • Specifications and Characteristics
  • Main Functions
  • Installation and Commissioning
  • System Design Requirements
  • Battery Connection Method
  • On-site Commissioning
  • Operating Interface Description
  • Printer Paper Installation and Use
  • Common Fault Analysis and Maintenance

Specifications

Operating temperature0 - 49 °C
Operating relative humidity0 - 93% RH @ 32 °C
AC powerAC220V 50Hz
Battery24V 12AH
Auxiliary 24VDC output current500mA normal supervision, 1200mA alarm
Relay contact rating2A 30VDC
NAC circuits4 NAC circuits, 8A total
Maximum NAC load2A per NAC circuit
FW962R sounder/strobes per NAC circuitUp to 50
Network capacityUp to 99 controllers
Communication protocolCAN
Loop capacityUp to 200 field devices
Loop output voltage20.2V ~ 26.2V
Loop card maximum current0.4A
Maximum distance to farthest field deviceLess than 1000 m
Grounding resistanceLess than 4 ohms

Frequently asked questions

How many controllers can the FW109 network support?

Up to 99 controllers can be networked.

How many field devices can each loop support?

Each loop can carry up to 200 field devices, with alarm and linkage points mixed on the loop.

What communication protocol is used for controller networking?

The controller networking uses CAN.

What is the maximum wiring distance to the farthest field device?

The wiring distance from the controller to the farthest field device must be less than 1000 meters.

Download PDF (1.4 MB)