LTL10 miniature liquid tuning fork is a limit switch for various liquids, suitable for storage tanks, containers, pipes. It can be used as a replacement for float switches, applied to piling, disturbance, liquid flow and bubbles.
The LTL10 is a miniature liquid tuning fork level switch from 中仪知联 (Zhongyi Zhilian (Wuxi) Industrial Automation Technology Co., Ltd.). It uses piezoelectric elements to drive and detect the vibration of the fork; when the fork contacts the measured liquid the resonant frequency drops, and the detection circuit evaluates this change and outputs a switching signal. The document states it can be used in tanks, containers and pipes, is not affected by conductivity, buildup, turbulence, flow or bubbles, and is not intended for hazardous areas or media hotter than 150 °C.
This operating manual (document number BA-LTL10-20220118) walks through the product description and working principle, installation guidance with correct and incorrect mounting examples, electrical connection for relay, PNP and NPN wiring, commissioning with the SET key and the fork status indication, fault analysis and maintenance, technical parameters, a dimension drawing, packaging, transport and storage, and the LTL10 model selection table. This manual is written in Chinese.
| Supply voltage | 19 to 60 VDC, 50/60 Hz |
|---|---|
| Switching time | < 1 s when covered by the medium |
| Ambient temperature | -40 to +80 °C |
| Storage temperature | -40 to +85 °C |
| Medium temperature | -40 to +150 °C |
| Operating pressure | -1 to 40 bar |
| Process connection | G1/2, G3/4, G1, NPT1/2, NPT3/4 |
| Electrical connection | Pg11, NPT1/2, M12, QUICKON |
| Housing material | Stainless steel S304 |
| Fork material | Stainless steel S304 / S316 |
| Output types | Relay output (250 VAC/4 A, 60 VDC/4 A), open collector NPN 400 mA, open collector PNP 400 mA |
| Power consumption | 0.25 W at DC supply, 1.5 W at AC supply |
The switching time is less than 1 s when the fork is covered by the medium.
The medium temperature range is -40 to +150 °C, and the manual notes the switch is not for media hotter than 150 °C.
Put the fork into the measured product, determine the alarm position, then press and hold the SET key, or hold a magnet against SET, for 3 seconds until the green light comes on.
The factory setting uses the density of water (1 g/cm³) as the reference for state switching; media with a density of 1 g/cm³ or more work without re-teaching, lighter media require a new setting.
Brown is supply positive, blue is supply negative, black is NO, white is COM and gray is NC.