The IPM300 series comprehensive measurement and control device is mainly used for measurement and control applications for unit devices, and can also be configured as a centralized measurement and control application. The main functions of the device include: switch signal acquisition, pulse signal acquisition, encoder signal acquisition, temperature signal acquisition, DC signal acquisition, AC signal acquisition, switch output control, analog output/remote adjustment, SOE event sequence record, synchronization, transformer tap adjustment and slide switch lock, graphical logic programmable function.
This manual covers the IPM300 series comprehensive measurement and control device, designed for unit device monitoring and control applications. It includes features such as signal acquisition, control output, SOE event recording, and graphical logic programming. The device consists of modular components connected via CAN bus, including DI, DO, RTD, SIG, DIO, and AC modules. The device supports flexible configuration with interchangeable modules and multiple communication interfaces.
The manual details technical parameters, module specifications, and configuration options for the device, including voltage, current, temperature, and signal input/output capacities. It also covers installation, configuration, and troubleshooting for the device and its modules. This manual is written in Chinese.
| Rated Input Voltage | 220V or 110V (order specified) |
|---|---|
| Rated Output Voltage | +5V, +24V |
| AC Voltage Range | 100V, 3/100V or 220V, 400(380)V |
| AC Current Range | 5A or 1A (order specified) |
| Frequency | 50Hz/60Hz |
| Power Consumption | ≤60W for 19-inch cabinet, ≤45W for 19/2-inch cabinet |
| Accuracy | ±0.2% for AC current/voltage, ±0.5% for power/energy, ±1℃ for RTD temperature |
| SOE Resolution | ≤1ms |
| Remote Control Accuracy | 100% |
| Overload Capacity | 2x rated current continuous, 10x for 10s, 40x for 1s |
The device supports dual high-speed Ethernet (electrical or optical), dual serial ports, IEC 60870-5-103, and Modbus/TCP protocols.
The AC voltage input range is 100V, 3/100V, or 220V, 400(380)V.
The AC current input range is 5A or 1A, depending on the order specification.
The accuracy for AC current and voltage measurements is ±0.2%.