About this manual

The document is an instruction book for a voltage disturbance generator from Beijing Bodian Xinli Electric. It starts with safety notices for installation, commissioning, operation, and maintenance, then describes the system structure, front panel, test wiring, technical parameters, control software, and data analysis software.

The device performs voltage disturbance characteristic tests and consists of a disturbance generator, data acquisition and recording, and data analysis. The disturbance generator can simulate voltage sags and swells, and the NI-based acquisition system can collect up to 16 channels with sampling from 10 kHz to 200 kHz. The analysis software displays recorded waveforms and can export results as CSV or Excel files. This manual is written in Chinese.

What's inside

  • Safety Notices
  • Product Overview
  • Technical Features
  • Reference Standards
  • System Description
  • Front Panel Operation
  • Test Wiring
  • Technical Parameters
  • Control Software
  • Data Analysis Software

Specifications

Rated voltage380 V with neutral or without neutral; or 220 V with three single-phase units used at the same time
Rated frequency50 Hz ± 0.5 Hz
Rated capacity20 kVA
Rated current30 A
Voltage disturbance functionsVoltage sag, voltage swell, voltage interruption
Voltage adjustment rangeSag: 0–100% UN; swell: 100–130% UN
Voltage adjustment step≤10%
Duration20 ms–60 s, adjustable
Switching deviceIGBT
Switching time<30 µs
Sag/swell phase angle0–360°, 1° step
Data acquisition channelsUp to 16
Sampling frequency10 kHz–200 kHz
Acquisition accuracyBetter than 0.05%
Disturbance generator output range0–1.3 p.u.

Frequently asked questions

What voltage range can the disturbance generator output?

The disturbance generator can output from 0 to 1.3 p.u.

Which voltage disturbance functions does the device provide?

It provides voltage sag, voltage swell, and voltage interruption.

How many channels can the data acquisition system record?

It can collect up to 16 channels.

What file formats can the analysis results be saved in?

The software can save results as CSV files or xls files.