Hongyutai HYT400 Mine Permanent Magnet Switch Controller User Manual

HYT400 mine permanent magnet switch controller is a kind of intelligent equipment used for 6KV, 10KV, 35KV distribution lines of various permanent magnet vacuum contactors, circuit breakers, reclosers, and mine vacuum circuit breakers to control the closing and opening process of permanent magnet switches.


Hongyutai HYT400 Mine Permanent Magnet Switch Controller User Manual - cover page
Brand
弘宇泰
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
7
File format
PDF
File size
1 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
CDCE810B0327DC026C9AB9984343C68E

About this manual

The HYT400 mine permanent magnet switch controller is used in 6 kV, 10 kV, and 35 kV distribution lines for permanent-magnet vacuum contactors, circuit breakers, reclosers, and mine vacuum circuit breakers. It controls closing and opening of the permanent-magnet switch and is available in MD, MS, CD, and CS variants for different capacitor and coil arrangements.

The manual describes adjustable closing and opening current, controllable closing, wide AC input range, automatic opening and capacitor discharge on power loss or undervoltage, terminal definitions, application wiring, indicator lamps, installation dimensions, and operating precautions. This manual is written in Chinese.

What's inside

  • Introduction
  • Features
  • Main technical parameters
  • Terminal definitions
  • Application wiring diagram
  • Indicator lamp description
  • Installation dimensions
  • Precautions

Specifications

Applicable permanent-magnet mechanismSingle (double) stable, single (double) coil
Input working voltageAC60-150 V
Capacitor charging voltageRegulated, adjustable DC100-210 V
Capacitor charging currentLess than 2 A
Static standby power consumption5 W or less
Maximum closing/opening drive current100 ms, DC60 A or DC160 A
Closing alarm voltageAdjustable DC100-200 V
Signal output0.5 A 125 VAC, 0.2 A 110 VDC
Operating environment-30 C to 85 C
Maximum outer dimensions205 x 150 x 38 mm

Frequently asked questions

What input voltage range can the HYT400 controller work with?

It can work normally from AC60 V to AC150 V.

What happens when AC 100 V input power is lost or undervoltage occurs?

It can automatically open, lock closing, and discharge the capacitor to 0 V within 2 minutes.

What are the operating temperature limits?

The operating temperature range is -30 C to 85 C.

What are the outer dimensions of the controller?

The outer dimensions are 205 x 150 x 38 mm.