Jiemai R4042 Data Acquisition Module User Manual

R4042 is a module with network data acquisition and control functions. It provides analog-to-digital, digital-to-analog, digital input/output, timer/counter and other functions. These modules can be remotely controlled by a series of instructions.


Jiemai R4042 Data Acquisition Module User Manual - cover page
Brand
Jiemai
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
40
File format
PDF
File size
144 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
B9080C3A8DD1A9F6EF92268ADD7F9E27

About this manual

The R4042 is a 13-channel collector output module in the R4000 series of network data acquisition and control modules from Beijing Jiemai Communication Equipment Co., Ltd. (北京捷麦通信器材有限公司). The series provides analog-to-digital, digital-to-analog, digital input/output, timer/counter and other functions, and the modules can be controlled remotely through a set of commands.

This user manual describes the module's terminal assignment, structure diagram, wiring, default settings and configuration table, then documents three command groups: the general command set, the conventional (output) command set and the host watchdog command set, including how checksums are built. Application notes at the end cover the INIT* terminal, module status, the dual watchdog, reset state, digital output states and latched digital input. This manual is written in Chinese.

What's inside

  • 概述
  • 端子分配
  • 结构图
  • 接线说明
  • 默认设置
  • 设置列表
  • 通用指令集
  • 常规指令集
  • 主看门狗指令集
  • 应用注意

Specifications

Output channels13
IsolationPower-to-ground isolation, 3750 Vrms
Maximum load voltage30 V
Maximum load current100 mA
Input power+10 to +30 VDC
Power consumption0.5 W
Default baud rate9600 bps
Default mode40 (DIO module)

Frequently asked questions

What are the factory default settings of the R4042 module?

The default address is 01, the baud rate is 9600 bps, the DIO module uses mode 40 and parity is disabled.

How many output channels does the R4042 have and what load can they drive?

It has 13 collector output channels, with a maximum load voltage of 30 V and a maximum load current of 100 mA.

What supply voltage does the R4042 need?

It takes +10 to +30 VDC input power and consumes 0.5 W.

How is the checksum of a command calculated?

Add the ASCII codes of all characters in the command or response except the (cr) terminator, then take the low 8 bits of the total.

Download PDF (144 KB)