Lingchen LC1200 Series PLC Hardware Function Manual

LC1200 series PLC hardware function manual, is a general-purpose motion controller launched by LCT Technology Co., Ltd., which combines CODESYS industrial automation software platform to integrate motion control technology and information technology in one, better serving non-standard automation, 3C, photovoltaic, logistics, lithium battery and other industries.


Lingchen LC1200 Series PLC Hardware Function Manual - cover page
Brand
凌臣
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
32
File format
PDF
File size
1.7 MB
Published
29 October, 2023
Updated
29 October, 2023
MD5 checksum
0E91E184CACB5474D79DAEEE4C75AF36

About this manual

This manual covers the Lingchen LC1200 Series, a general-purpose motion controller built on the CODESYS platform with an Arm Cortex A7 dual-core processor and an RT-Linux operating system. It describes the controller's hardware configuration, its 32 I/O points (16 inputs and 16 outputs), the three network ports supporting EtherCAT, EtherNet/IP, OPC UA and Modbus TCP, and EtherCAT motion control for 8, 16 or 32 axes.

The document also explains the model nameplate code (for example LC1208-CPU20TN), the product specifications, and installation on a DIN rail. Wiring chapters cover the 24 V DC power supply, CPU module input/output wiring and serial/Ethernet communication, followed by operation and maintenance sections on RUN/STOP control, indicator lights, the reset key, SD card use and routine servicing. This manual is written in Chinese.

What's inside

  • Product Overview
  • Model Nameplate Information
  • Structure and Dimensions
  • Hardware Configuration and Technical Parameters
  • Software Configuration and Technical Parameters
  • Installation Environment and Mounting on DIN Rail
  • Power Supply Wiring
  • CPU Module Input/Output Wiring
  • CPU Module Communication Wiring (Ethernet, RS485, OPC UA, EtherNet/IP)
  • Operation, Indicators, Reset Key and Maintenance

Specifications

ProcessorArm Cortex A7 dual-core
Memory1 GB DDR3 RAM (board-mounted)
Flash8 GB (board-mounted)
Network ports3 ports supporting EtherCAT, EtherNet/IP, OPC UA, Modbus TCP
Digital I/O32 points: 16 transistor inputs and 16 transistor outputs
High-speed inputs12 high-speed inputs, 200 kHz response frequency
High-speed outputs12 high-speed outputs, 200 kHz response frequency
Serial ports1 isolated RS232, 2 isolated RS485 (Phoenix terminals)
Power supply24 V DC (±20 %), 1 A
Operating / storage temperature0…+50 °C / -40…+75 °C
Protection classIP 20
Operating systemLinux 4.14 with RT kernel patch
Motion control axes8, 16 or 32 axes via EtherCAT
SD cardMaximum 32 GB
RTC battery backup180 days with power off
EtherNet/IP minimum cycle (RPI)5 ms

Frequently asked questions

How many I/O points does the LC1200 Series PLC support?

The hardware supports 32 I/O points, consisting of 16 inputs and 16 outputs. Twelve of the inputs and twelve of the outputs are high-speed points rated at a 200 kHz response frequency.

What are the default IP addresses of the LC1200 network ports?

After a factory-IP reset the ports default to 192.168.0.99 (CN1), 192.168.2.99 (CN2) and 192.168.8.99 (EtherCAT). The current addresses can be checked with the GetIp eth0, eth1 and eth2 instructions.

How do I reset the PLC to its factory IP address?

Press the reset button for more than 6 seconds to restore the factory IP; pressing it for 2 to 6 seconds deletes the device program and user management.

Which IEC 61131-3 programming languages are supported?

The controller supports six general programming languages: LD, IL, ST, SFC, CFC and FBD.