HMLH-7Y SF6 gas recovery and purification device instruction manual, details the product's purpose, model, main technical parameters, working principle and structural features, pre-start work, operation instructions and precautions, maintenance and maintenance, common faults and elimination methods, after-sales service and other content.
This manual provides detailed instructions for operating the HMLH-7Y SF6 gas recovery and purification device, including setup, operation, maintenance, and troubleshooting. It covers technical specifications, working principles, safety precautions, and maintenance procedures for handling SF6 gas in electrical equipment.
The device features recovery, charging, purification, vacuum extraction, storage, and bottle-filling functions. It uses a refrigeration liquefaction method and includes safety controls such as pressure limiters and safety valves to ensure safe operation. This manual is written in Chinese.
| Recovery Initial Pressure | ≤0.8MPa |
|---|---|
| Recovery Final Pressure | ≤50KPa |
| Recovery Time | Less than 2.5 hours for 1m³ SF6 from 0.8MPa to 50KPa |
| Charging Time | Less than 0.8 hours to charge 1m³ SF6 from 133Pa to 0.8MPa |
| Vacuum Limit | ≤10 Pa |
| Storage Capacity | 0.015m³ |
| Noise Level | ≤75dB(A) |
| Operating Temperature | -10°C to 40°C |
| Power Supply | Three-phase AC 50Hz 380V±10% |
| Weight | Approx. 400 kg |
| Dimensions | 1360×800×1300 mm |
The maximum storage pressure is 3.8 MPa.
The noise level is ≤75dB(A).
The operating temperature range is -10°C to 40°C.