Kingser JKWTD Dynamic Reactive Power Compensation Controller User Manual

This is a dynamic reactive power compensation controller that can compensate the power factor through the setting function and has protection functions, real-time data communication functions, data management functions, over-limit and fault alarm functions, etc.


Kingser JKWTD Dynamic Reactive Power Compensation Controller User Manual - cover page
Brand
Kingser
Category
power system
Document type
User Manual
Language
Chinese
Pages
8
File format
PDF
File size
1.7 MB
Published
29 October, 2023
Updated
29 October, 2023
MD5 checksum
4639B05361A41F64EADA9E320102A5AA

About this manual

This document provides detailed instructions for installing, configuring, and troubleshooting the Kingser JKWTD dynamic reactive power compensation controller. It covers display functions, parameter settings, compensation control, protection features, data communication, and fault diagnosis. The controller is designed for 0.4kV, 50Hz AC power systems and features a 32-bit ARM MCU for real-time monitoring and control.

The manual includes technical specifications, installation dimensions, communication protocols (RS-485, MODBUS), and step-by-step troubleshooting for common issues such as no display, incorrect COSØ readings, or poor compensation performance. This manual is written in Chinese.

What's inside

  • Product Overview
  • Model Description
  • Usage Conditions
  • Product Dimensions and Installation
  • Basic Functions
  • Technical Parameters
  • Installation and Debugging
  • Unboxing Check
  • Simple Fault Troubleshooting

Specifications

Operating VoltageAC 0.4kV, 50Hz
Display TypeDigital tube display
Controller Core32-bit ARM MCU
Installation Dimensions143mm × 143mm × 100mm
Mounting Hole Size138mm × 138mm
Mounting Depth96mm
Communication InterfaceRS-485
Communication ProtocolMODBUS
Control Outputs16 channels, AC220V, 5A
Operating Temperature-20℃ to +70℃
Relative Humidity20% to 90% at 40℃
Altitude≤2500 meters

Frequently asked questions

How do I troubleshoot if the controller does not display anything?

Check if the power cable is properly connected.

What should I do if the COSØ value does not change with capacitor switching?

Check if the current transformer position is correct (sampling current = load current + capacitor current).

What is the default target power factor for compensation?

The default target power factor is 0.99.