This is a dynamic reactive power compensation controller that can compensate the power factor through the setting function and has protection functions, real-time data communication functions, data management functions, over-limit and fault alarm functions, etc.
This document provides detailed instructions for installing, configuring, and troubleshooting the Kingser JKWTD dynamic reactive power compensation controller. It covers display functions, parameter settings, compensation control, protection features, data communication, and fault diagnosis. The controller is designed for 0.4kV, 50Hz AC power systems and features a 32-bit ARM MCU for real-time monitoring and control.
The manual includes technical specifications, installation dimensions, communication protocols (RS-485, MODBUS), and step-by-step troubleshooting for common issues such as no display, incorrect COSØ readings, or poor compensation performance. This manual is written in Chinese.
| Operating Voltage | AC 0.4kV, 50Hz |
|---|---|
| Display Type | Digital tube display |
| Controller Core | 32-bit ARM MCU |
| Installation Dimensions | 143mm × 143mm × 100mm |
| Mounting Hole Size | 138mm × 138mm |
| Mounting Depth | 96mm |
| Communication Interface | RS-485 |
| Communication Protocol | MODBUS |
| Control Outputs | 16 channels, AC220V, 5A |
| Operating Temperature | -20℃ to +70℃ |
| Relative Humidity | 20% to 90% at 40℃ |
| Altitude | ≤2500 meters |
Check if the power cable is properly connected.
Check if the current transformer position is correct (sampling current = load current + capacitor current).
The default target power factor is 0.99.