This manual provides detailed instructions on installing and maintaining the Fireboy Engine Shutdown/Override System.
The Fireboy-Xintex Series 3000, 5000, and 8000 engine shutdown/override systems are designed to automatically shut down engines, generators, and blowers when a Fireboy automatic extinguishing system discharges. The system includes a pressure switch at the extinguisher, a relay terminal box at the helm, and an instrument display unit that provides visual and audible status indication plus an override switch to restart engines after discharge or prevent shutdown in crowded waterways.
Installation requires a qualified marine electrician and compliance with ABYC standards. Wiring uses #16 stranded copper wire with insulated crimp terminals. The manual details connections for gasoline and diesel engines, system testing procedures, load limitations (ES models: 10 A DC continuous at 12 Vdc; ELS models: 10 A on auxiliary contacts, 2 A on engine relays at 11–32 Vdc), and an optional time-delay mode for ELS-5510 and ELS-8510 models that cycles engine relays for approximately 15 seconds after discharge.
| ES model continuous load | 10 amps DC (30 amp available on request) |
|---|---|
| ES model operating voltage | 12 Vdc (24 V and 32 V available on request) |
| ELS model auxiliary contact load | 10 amps DC continuous per contact |
| ELS model engine relay load | 2 amps DC continuous per relay |
| ELS model operating voltage range | 11–32 Vdc |
| Wiring gauge | #16 stranded copper wire |
| Terminal stud size | #6 |
| Time delay duration (ELS-5510/8510) | approximately 15 seconds |
ES models operate at 12 Vdc, with 24 V and 32 V models available upon request.
Bottle switches must be wired in series so that either extinguisher can activate the shutdown/override system.
Engine contacts switch state for approximately 15 seconds and then return to their resting state.