This document is Chapter 8 of Iowa Storm Water Management Manual, which introduces design, calculation, design elements and maintenance of permeable pavement systems
This manual provides detailed guidance on permeable pavement systems including permeable pavers, pervious concrete, and porous asphalt. It covers design criteria, construction methods, maintenance practices, and site constraints for effective stormwater runoff reduction in Iowa. The document includes technical specifications, calculation protocols, and inspection checklists for implementation by engineers and contractors.
| Minimum Water Table Separation | 2 feet |
|---|---|
| Design Storm | Defined in design criteria section |
| Soil Infiltration Rate Threshold | Less than 1 inch/hour |
Permeable pavers (PP), pervious concrete (PC), and porous asphalt (PA) are common systems suitable for Iowa.
Permeable pavers (PP), pervious concrete (PC), and porous asphalt (PA), or open grid pavers.
Minimum 2 foot separation from top of subgrade to seasonal high water table.
The void space of porous asphalt is approximately 15-18%, as opposed to 2-3% for conventional asphalt.