Oventrop 1 Cocon QTZ PN 16 Pressure independent control valve product instruction manual, introduces the characteristics and uses of the product.
This document provides technical specifications, installation instructions, and maintenance guidelines for the Oventrop Cocon QTZ PN 16 pressure-independent control valve. It details flow control, differential pressure settings, compatible actuators, and material specifications. The valve is designed for closed-loop heating and cooling systems and can be adjusted via handwheel or actuator. Installation requires proper orientation, clean piping, and strainer use. Maintenance includes gland replacement under operating conditions.
The manual includes dimension tables, control range data, and pressure test procedures using the OV-DMC 3 system. Accessories like insulation shells and adapters are listed with item numbers. The valve supports various DN sizes and flow rates, with presetting secured by a locking ring and lead seal.
| Max. operating temperature | 120 °C |
|---|---|
| Min. operating temperature | -10 °C |
| Max. operating pressure | 16 bar (1600 kPa) |
| Fluid compatibility | Water or mixtures of water and ethylene/propylene glycol (max. 50 %), ph value 6.5-10 |
| Materials | Body: dezincification resistant brass, seals: EPDM or PTFE, valve stem: stainless steel |
| Closing force (actuator) | 90 - 150 N |
| Connection thread | M 30 x 1.5 |
| Control piston stroke (DN 20) | 3.5 mm |
Max. operating pressure: 16 bar (1600 kPa).
Water or mixtures of water and ethylene/propylene glycol (max. 50 %), ph value 6.5-10.
The required flow rate can be set at the handwheel and secured with a locking ring.
Body: dezincification resistant brass, seals: EPDM or PTFE, valve stem: stainless steel.