This is a manual that introduces the operation, servicing and safety procedures associated with the Jumbo Low Profi le Ball Intake Valve.
This instruction manual from Task Force Tips, Inc. covers the Jumbo Low Profile Ball Intake Valve Series, including models AXD1ST-NX-T, AZD1ST-NX-T, AXD1ST-NX-F, and AZD1ST-NX-F. It is intended to familiarize firefighters and maintenance personnel with operation, servicing, and safety procedures.
It includes safety information, specifications, installation steps, operating instructions, exploded views and parts lists, troubleshooting, maintenance procedures, and details on the ten-year extended warranty for JBIV-LP series valves.
| Waterway Size | 5.25” (133mm) |
|---|---|
| Max Pressure | 250 psi (17 bar) |
| Min Pressure | Full Vacuum |
| Temperature Rating | -25°F to 135°F (-32°C to 57°C) |
| NFPA 1962 Test Pressure | 300 PSI (21 bar) |
The maximum operating pressure is 250 PSI (17 bar), and it must not be exceeded on either side of the valve.
Use with salt water is permissible provided the valve is thoroughly cleaned with fresh water after each use.
It takes six seconds from open to close, meeting the NFPA 1901 slow close requirement.
The valve may become damaged if allowed to freeze while containing water, so it should always be drained after use.