This document describes how to use the Manual J Abridged Edition (AE) forms to calculate the load for a heating, ventilation, and air conditioning (HVAC) system and to select a heat pump.
This document explains how to understand and use an HVAC design review form for a Manual J Abridged Edition (AE) load calculation and heat pump equipment selection. It shows a sample completed review form, the Manual J1AE room-by-room load form, and Worksheet B for windows and glass doors.
It also includes sample heat pump cooling and heating performance data and a Manual D friction rate worksheet used to determine available static pressure, total effective length, and friction rate. The text notes that Manual J1AE calculations must meet the requirements on the Alternative Abridged Edition Check List.
They are valid when they meet all of the requirements on the Alternative Abridged Edition Check List.
It condenses the basic elements of the load calculation into a functional procedure to promote comprehension in students.
Available static pressure equals external static pressure minus total component losses; the sample uses 0.75 minus 0.40 IWC.
It is the sum of the supply-side TEL and the return-side TEL.