This document is the installation, operation, and maintenance manual for MUA Controls modular electric heaters and inserts.
This manual covers MUA Controls standard and modular electric heaters and inserts. It documents receiving and inspection, warranty terms, and mechanical and electrical installation for roof mount, duct mount, indoor inline, and heat module add-on applications.
It also covers operation through the remote HMI control panel, menu configurations, motor speed control, motorized intake damper, VFD installation and programming, SCR electrical control, and network options including BACnet and LonWorks. Start-up, troubleshooting, and maintenance sections include airflow troubleshooting, general maintenance intervals, unit filters, and start-up documentation.
| Warranty period | 2 years from date of shipment |
|---|---|
| Electric heater power inputs | Two |
| Minimum distance from exhaust vents to inlet | 10 feet |
| Minimum fasteners to secure fan to curb | Eight lug screws, anchor bolts, or other suitable fasteners |
| Maximum roof opening | 2 inches smaller than curb outside dimension |
| Load requirement formula | KW = (CFM x Temperature Rise) / 3160 |
Installation should only be performed by a qualified professional who has read and understands the instructions and is familiar with proper safety precautions.
The equipment is warranted for 2 years from date of shipment under normal use and service.
Electric heaters have two power inputs; the external disconnect interrupts power to the motor and controls only.
Check for interior and exterior damage and verify that all accessory items are accounted for and damage free.