This document introduces the installation, connection and operation methods of the Optidrive E3 IP66 outdoor variable frequency drive
This quick start guide covers the Optidrive E3 IP66 (NEMA 4X) AC variable speed drive, rated 0.37 kW – 22 kW / 0.5 HP – 30 HP, for 110 V and 230 V single phase input or 230 V and 480 V three phase input. It walks through eight steps: check, prepare, mount, connect, check, power on, commission and operate. It states that the drive should only be installed by a qualified electrician and that detailed installation, safety and operational instructions are in the Optidrive E3 IP66 Outdoor User Manual.
The guide explains how to identify the drive from its model number, where to mount it, mechanical dimensions and weights by frame size, cable gland sizes, power and control terminal wiring, motor terminal box connections, UL compliance requirements and motor thermistor connection.
| Power range | 0.37 kW – 22 kW / 0.5 HP – 30 HP |
|---|---|
| Input voltage | 110 V & 230 V single phase; 230 V & 480 V three phase |
| Enclosure rating | IP66 (NEMA 4X) |
| Input supply voltage tolerance (230 V units) | 200 – 240 V RMS, ±10%, max 240 V RMS |
| Input supply voltage tolerance (400 V units) | 380 – 480 V, ±10%, max 500 V RMS |
| Supply frequency | 50 – 60 Hz ±5% |
| Maximum short circuit capacity | 100 kA symmetrical with Class J fuses |
| Motor cable | 75°C copper |
| Control cable conductor size | 0.05 – 2.5 mm2 / 30 – 12 AWG |
| Control terminal tightening torque | 0.5 Nm maximum |
| Power terminal tightening torque | 1.5 Nm (13 lb-in) |
| Compatible thermistor | PTC type, 2.5 kΩ trip level |
It supports 110 V and 230 V single phase input, or 230 V and 480 V three phase input.
It covers 0.37 kW – 22 kW, or 0.5 HP – 30 HP.
They are in the Optidrive E3 IP66 Outdoor User Manual; this quick start guide does not provide them.
Control cable entry conductor size is 0.05 – 2.5 mm2 / 30 – 12 AWG.