This document introduces the functions and usage methods of SK-HEAT-W/SK-HEAT-ROR-W/SK-HEAT-HT-W intelligent programmable temperature sensors.
Silent Knight SK-HEAT-W, SK-HEAT-ROR-W and SK-HEAT-HT-W are field-programmable intelligent temperature sensors for fire alarm systems. They use a thermistor sensing circuit and provide open-area protection with 50-foot spacing as approved by UL 521, and they can be programmed through a compatible control panel as a 135°F fixed, rate-of-rise/135°F fixed, or 190°F high-temperature sensor. Each sensor has two LEDs and rotary dial switches for setting its address.
The instructions cover wiring the sensor base, setting the address, installing the sensor, and applying power. They also describe tamper resistance, testing with an optional test magnet or a 1000–1500 W hair dryer, cleaning with a vacuum or compressed air, FM classification, FCC compliance, and technical specifications. The sensors require compatible addressable communications and listed-compatible control panels.
| Operating Voltage Range | 15 to 32 Volts DC |
|---|---|
| Peak Operating Current | 200 uA @ 24 VDC |
| Maximum Alarm Current | 2 mA @ 24 VDC |
| Maximum Current | 4.5 mA @ 24 VDC |
| Operating Humidity Range | 10% to 93% Relative Humidity, Non-condensing |
| Fixed Temperature Rating | 135°F (57°C) |
| High Heat Temperature Rating | 190°F (88°C) |
| Rate-of-Rise Detection | Responds to greater than 15°F/minute or 135°F |
| Height | 2.0˝ (51 mm) installed in B300-6 Base |
| Diameter | 6.2˝ (156 mm ) installed in B300-6 Base |
| Weight | 3.4 oz. (95 g) |
| Listing | UL 521 listed for Heat Detectors |
The SK-HEAT-W defaults to a 135°F fixed heat detector, the SK-HEAT-ROR-W defaults to 135°F fixed plus rate-of-rise, and the SK-HEAT-HT-W defaults to a 190°F high-temperature heat detector.
Use the rotary dial switches on the sensor to set the desired address; devices are point addressable up to 159 addresses.
It can be tested with an optional test magnet or by directing heat from a 1000–1500 W hair dryer toward the sensor from about 6 inches away.
Remove dust and debris from the sensing area with a vacuum cleaner or compressed air, then reinstall and test the detector.