Sol-Ark 12K Outdoor Inverter Installation Guide

This manual is the installation manual for the 12K inverter, which introduces the composition, installation steps, circuit diagrams, software settings and other contents of the inverter.


Sol-Ark 12K Outdoor Inverter Installation Guide - cover page
Brand
sol-ark
Category
inverter
Document type
Installation Guide
Language
English
Pages
54
File format
PDF
File size
9.4 MB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
748044F2E6EC03301BA4AD37F1057ECF

About this manual

This guide provides detailed instructions for installing the Sol-Ark 12K outdoor inverter, covering physical mounting, wiring diagrams, battery and solar panel integration, and remote monitoring setup. It includes safety warnings, torque specifications, and troubleshooting for common errors. The document is specific to outdoor models and includes guidance for both grid-tied and off-grid installations, with special attention to phasing and sensor configurations.

The guide also covers error codes, such as F18 for AC overcurrent and F26 for bus imbalance, with remedies for each. It includes wire gauge recommendations, component lists, and notes on grounding and polarity to prevent damage. Remote monitoring via Wi-Fi and IP address setup are also addressed, along with parallel system configurations and troubleshooting for phasing issues.

What's inside

  • Physical Installation
  • Wiring Diagrams
  • Battery Integration
  • Solar Panel Connection
  • Generator Integration
  • Remote Monitoring Setup
  • Programming Guide
  • Troubleshooting
  • Error Codes
  • Installation Verification Checklist

Specifications

Torque ValuesLoad Breaker: 26.5 IN Lbs / 3 NM; Grid Breaker: 26.5 IN Lbs / 3 NM; Gen Breaker: 26.5 IN Lbs / 3 NM; Neutral / Ground Busbars: 26.5 IN Lbs / 3 NM; Cover Screws: 26.5 IN Lbs / 3 NM; Battery Connection: 90.0 IN Lbs / 10 NM
Temperature DeratingDC: 90C-100C Shutdown @ 100C; AC: 75C-82C Shutdown @ 82C
Wire Gauge GuidePV input: 10AWG; All AC Inputs/Outputs: 6-4AWG; All Sensors: 20-24AWG; CT Sensors: 10' Wire Included; Batt Temp Sensor: 6' Wire Included; RJ45 Cable: 7' Included (Extendable up to 20'); Battery input: 2/0-4/0AWG (3/8" Lugs)

Frequently asked questions

What is the maximum voltage for PV input on the Sol-Ark 12K?

DO NOT exceed 500Voc on any MPPT on the Sol-Ark.

How should I handle grounding for the Sol-Ark 12K?

Ground MUST be bonded to Neutral ONLY ONCE in the circuit. Solar PV+/PV- are UNGROUNDED.

What should I do if the Sol-Ark screen shows 'Grid Phase Wrong'?

Measure L1 to L1 (Top Screws) between the Grid and Load breaker; you should see 0V AC. Repeat for L2 to L2. Correct wiring until you read 0V AC between both pairs.

What is the remedy for error code F18?

Overloaded the Load Output (reduce loads) or overloaded a generator (reduce Gen Start A see pg. 33). Wiring Short on the AC Side can also cause this error.