Altronix 602ULADA, 602ULADAJ, 802ULADA, 802ULADAJ, 1002ULADA, 1002ULADAJ and R1002ULADA are very versatile devices. They can be used with or without specific synchronization modules provided by some manufacturers. Multiple units can be synchronized by using either the built-in sync mode or a external synchronization module. Please note, that only notification appliances with synchronization capabilities can be synchronized. Units can operate with either one (1) or two (2) outputs from the FACP.
This document serves as an application guide for Altronix NAC Power Extenders, specifically models AL602ULADA, AL802ULADA, AL1002ULADA, and R1002ULADA. It provides instructions on general information, Class A and Class B hookups, and the use of multiple units from a Fire Alarm Control Panel (FACP). The guide details how to wire these devices for various notification appliance circuits and explains synchronization capabilities.
| Compatible Models | AL602ULADA, AL802ULADA, AL1002ULADA, R1002ULADA |
|---|---|
| Compatible Sync Protocols | Amseco, Gentex, System Sensor, Wheelock |
| Enclosure Dimensions (BC400) | 15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm) |
| Enclosure Dimensions (BC600) | 18" x 14.5" x 4.5" (457.2mm x 368.3mm x 114.3mm) |
| Enclosure Dimensions (R1002ULADA) | 3.25" x 19.0" x 26.5" (82.6mm x 482.6mm x 673.1mm) |
Yes, the units have built-in protocols to support Amseco, Gentex, System Sensor, and Wheelock two-wire synchronizable devices, so an external sync module is not required.
The units can be used with up to four Class B circuits.
You may connect both Input 1 and Input 2 to it, which will activate both visual and audible notification appliances simultaneously.