This is a GEA Power Cooling cooling tower operation and maintenance manual, which mainly introduces the specifications, description, operating procedures, maintenance methods of the cooling tower
This manual provides detailed procedures for starting, operating, and shutting down the GRAY WATER BMP cooling tower. It covers water treatment, winter operation, and maintenance tasks including periodic inspections and troubleshooting. Appendices include spare parts pricing, performance curves, and mechanical equipment specifications.
The tower is a fiberglass plume-abated counterflow design with 11 cells, 30-ft fans, and a vacuum system for plume abatement. It includes specifications for materials, motors, fans, and control systems. Wind and seismic response procedures are also outlined for safety during extreme events.
| Tower Model No | 484854-11I-30-FPF |
|---|---|
| Water Circulation | 127,000 gpm |
| Inlet Water Temperature | 102.3 °F |
| Outlet Water Temperature | 76.5 °F |
| Design Wet Bulb Temperature | 41 °F |
| Fan Speed | 85 rpm |
| Fan Diameter | 30 ft |
| Rated Motor Capacity | 200Hp |
| Design Wind Velocity | 90 mph |
| Number of Cells | 11 |
The design wet bulb temperature is 41 °F.
The tower has 11 cells.
The fan speed is 85 rpm.
The rated motor capacity is 200Hp.