About this manual

This manual provides detailed procedures for starting, operating, and shutting down the GRAY WATER BMP cooling tower. It covers water treatment, winter operation, and maintenance tasks including periodic inspections and troubleshooting. Appendices include spare parts pricing, performance curves, and mechanical equipment specifications.

The tower is a fiberglass plume-abated counterflow design with 11 cells, 30-ft fans, and a vacuum system for plume abatement. It includes specifications for materials, motors, fans, and control systems. Wind and seismic response procedures are also outlined for safety during extreme events.

What's inside

  • Introduction
  • Operation Procedure
  • Maintenance Instructions
  • Appendices
  • Wind and Seismic Response Procedures

Specifications

Tower Model No484854-11I-30-FPF
Water Circulation127,000 gpm
Inlet Water Temperature102.3 °F
Outlet Water Temperature76.5 °F
Design Wet Bulb Temperature41 °F
Fan Speed85 rpm
Fan Diameter30 ft
Rated Motor Capacity200Hp
Design Wind Velocity90 mph
Number of Cells11

Frequently asked questions

What is the tower’s design wet bulb temperature?

The design wet bulb temperature is 41 °F.

How many cells does the tower have?

The tower has 11 cells.

What is the fan speed?

The fan speed is 85 rpm.

What is the rated motor capacity?

The rated motor capacity is 200Hp.