This manual is a guide for EZ-Gas burner installation and maintenance. It mainly includes the burner's safe use, installation, connection, debugging and maintenance.
This manual provides instructions for the installation, wiring, and startup of the Carlin EZ-Gas gas burner. It details site preparation, venting requirements, gas piping, and electrical connections, emphasizing compliance with local codes and standards such as ANSI Z21.17 and NFPA 70.
| Input | 50,000 to 275,000 Btuh |
|---|---|
| Fuels | Natural gas or propane gas |
| Max. supply pressure | 14 inches w.c. |
| Min. supply pressure | 5 inches w.c. |
| Manifold pressure | 3.5 inches w.c. |
| Power | 120V/60 Hz/1-Phase |
| Motor HP | 1/15, 1/7, or 1/6 HP |
| Ignition | Carlin Model 41800 solid state ignitor |
| Control | Carlin Model 60200FR microprocessor control |
This manual must be used only by a qualified service technician, or a licensed Plumber or Gas Fitter in Massachusetts.
The burner is designed for use with natural gas or propane gas.