American Concrete Institute ACI RAP-8 Installation of Embedded Galvanic Anodes User Manual

Field guide to the installation of embedded anodes


American Concrete Institute ACI RAP-8 Installation of Embedded Galvanic Anodes User Manual - cover page
Brand
American Concrete Institute
Document type
User Manual
Language
English
Pages
7
File format
PDF
File size
1.8 MB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
1B01BE7E706232A70813BD529B00F84F

About this manual

This document provides step-by-step instructions for installing embedded galvanic anodes to protect reinforcing steel in concrete repairs. It covers preparation, material selection, equipment, safety, and installation procedures for both Type 1 and Type 2 anodes. The guide emphasizes compatibility with low-resistivity repair materials and includes safety and regulatory compliance notes.

The guide is intended for owners, engineers, and contractors involved in concrete repair projects, particularly in chloride-contaminated or carbonated concrete environments. It explains how to mitigate the 'ring-anode' effect and offers practical installation methods for different repair scenarios.

What's inside

  • Introduction
  • Purpose and Use of Embedded Galvanic Anodes
  • Surface Preparation
  • Material Selection
  • Equipment Requirements
  • Safety Considerations
  • Preconstruction Meeting
  • Repair Procedure
  • Type 1 Anode Installation
  • Type 2 Anode Installation

Specifications

Resistivity RequirementLess than 15,000 ohm-cm
Minimum Clearance3/4 in. [19 mm] or 1/4 in. [6 mm] larger than nominal maximum aggregate size
Connection ResistanceLess than 1 ohm

Frequently asked questions

What is the purpose of installing embedded galvanic anodes?

Embedded galvanic anodes reduce the corrosion activity of reinforcing steel in the vicinity of the installed anode.

What materials are compatible with embedded galvanic anodes?

Embedded galvanic anodes should be used only with cementitious or cementitious-polymer repair materials with resistivity less than 15,000 ohm-cm.

What equipment is needed to install Type 1 anodes?

Basic hand tools and a DC ohm meter capable of reading 0 to 200 ohms.

Download PDF (1.8 MB)