This file is the DatranII Excel Owners Manual, which introduces the product functions and features, including revision details, table of contents, introduction, functionality, precautions, functional description, system status leds, error codes, power supply, digital inputs, digital outputs, analog inputs, analog outputs, modem and other contents.


QTech Q22 DATRAN II eXcel Module Owners Manual - cover page
Brand
q-Tech
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
63
File format
PDF
File size
1.4 MB
Published
21 October, 2023
Updated
21 October, 2023
MD5 checksum
7E11A91E3961AEBF9170E66A46A43A2D

About this manual

This manual provides operating instructions for the Q22 DATRAN II eXcel Module, an intelligent remote unit designed for SCADA base station communication or standalone point-to-point arrangements. It details the module's features, including a 16-bit processor and surface mount technology, and explains how to configure hardware settings via jumpers.

What's inside

  • Introduction
  • Functionality
  • System Status LEDs
  • Error Codes
  • Power Supply
  • Digital Inputs
  • Digital Outputs
  • Analog Inputs
  • Analog Outputs
  • Configuration

Specifications

Power Supply VoltageDC 11 to 28 volts
Current at 12V90mA
Current at 24V60mA
Digital Inputs TypeOpto Isolated, ground referenced, current sink inputs
Maximum Analog Input Voltage15 volts
Analog Output Current0…20mA, 4…20mA

Frequently asked questions

What is the low battery detection threshold for a 12V battery?

Power turns OFF at 10.5 volts and back ON at 11.5 volts.

What is the maximum sink current for the digital outputs?

The maximum sink current is 3 amps, limited to a total of 2 amps for all outputs by an internal fuse.

What processor is used in the Q22 module?

The module combines a completely new state of the art Q03 – 16 Bit Processor.