NTMA Epoxy Terrazzo Guide Specification

This is a guide specification for epoxy terrazzo


NTMA Epoxy Terrazzo Guide Specification - cover page
Brand
NTMA
Category
Industrial Supply
Document type
Product Leaflet
Language
English
Pages
2
File format
PDF
File size
46 KB
Published
21 October, 2023
Updated
21 October, 2023
MD5 checksum
EF13BD56CDBEEC44A231B6341CB1FD3A

About this manual

This document outlines the specifications for epoxy terrazzo installation, including material requirements, testing methods, and installation procedures. It covers primer, epoxy resin, marble chips, and finishing standards. The guide also includes quality assurance, submittal requirements, and warranty details. Compliance with NTMA standards is required for materials and installation.

What's inside

  • Materials
  • Quality Assurance
  • Submittal
  • Delivery, Storage and Handling
  • Guarantee
  • Installation
  • Inspection
  • Finishing
  • Cleaning and Sealing
  • Protection

Specifications

Hardness60-85 Shore D Durometer
Tensile Strength3,000 psi minimum
Compressive Strength10,000 psi minimum
FlammabilitySelf-extinguishing, extent of burning 0.25 inches maximum
Thermal Coefficient of Linear Expansion25 X 10, 6 inches per inch per degrees to 140 o Fahrenheit maximum
Bond Strength100% concrete failure minimum with 300 PSI minimum tensile strength
Abrasion and Impact ResistanceNot to exceed 40% loss
24 Hour Absorption RateNot to exceed 0.75 percent
Electrical Resistance (Conductive Floors)Less than 1,000,000 ohms and more than 25,000 ohms

Frequently asked questions

What is the flammability requirement for epoxy terrazzo?

The epoxy terrazzo must be self-extinguishing with a burning extent of no more than 0.25 inches.

What is the minimum ambient temperature required for epoxy terrazzo installation?

Ambient temperature shall be maintained at a minimum of 50 o Fahrenheit.

What is the required tensile strength for epoxy terrazzo specimens?

The tensile strength shall be 3,000 psi minimum.

What is the maximum allowable variation in a concrete subfloor?

The subfloor should not vary more than 1/4 inch in 10 feet.