Swema SwemaAir 5 Hot Wire Anemometer User Manual

SwemaAir 5 is a hot-wire anemometer for measuring air velocity and flow (airflow). The instrument has an integrated barometer, which together with the temperature sensor in the hot-wire probe compensates for the changing density of the air. In order to make the flow measurements in ducts accurate, it is possible to enter a K2 factor (duct factor) in the instrument, which compensates for the friction resistance along the duct wall in ventilation ducts, so that the flow is reduced in accordance with NVG (T22: 1998). The area can be entered either as a diameter, height x width, or the area directly. The maximum, minimum and average value for each measurement is displayed on the display. The instrument has a wide range of applications, for example for measuring air speed in ducts, draught from windows, air speed measurement over grates etc. For air speed, choose between m/s and fpm. For flow, choose between l/s, m3/h and CFM. All measurements can be stored in the instrument's memory and subsequently transferred to a PC via the free software, Swema Terminal3. SwemaAir 5 is supplied complete with calibration certificate (0.1…12 m/s), telescopic hot-wire probe, USB cable, rechargeable AA batteries and manual. Technical data Recommended calibration interval: 1 year or follow the instructions on the instrument.


Swema SwemaAir 5 Hot Wire Anemometer User Manual - cover page
Brand
Swema
Category
Other Electronics
Document type
User Manual
Language
DA
Pages
8
File format
PDF
File size
826 KB
Published
21 October, 2023
Updated
21 October, 2023
MD5 checksum
9E9527647D022C16FF3CB35923F6054E

About this manual

The Swema SwemaAir 5 is a hot wire anemometer designed for measuring air speed and flow (air current). The instrument features a built-in barometer and temperature sensor to compensate for changing air density, ensuring precise flow measurements in ducts. It supports various measurement units and allows data storage and transfer to a PC via USB using the free Swema Terminal3 software.

What's inside

  • Introduktion
  • Start af instrumentet
  • Målinger
  • Luftflowmåling
  • Barometrisk tryk og temperatur
  • Måletilstand
  • Grundlæggende indstillinger
  • Hukommelse

Specifications

Air speed range0.1... 12 m/s
Temperature range-20... 80°C
Barometer range600... 1200 hPa
Accuracy at 23°C±0,04 m/s at 0.1...1.33 m/s
Accuracy at 1.33...30 m/s±3% of read value
Temperature accuracy±0,3°C
Operating temperature0 ... 50 °C
Memory capacity300 measurements
Battery lifeUp to 150 hours
Dimensions195 x 93 X 36mm with sensor
Weight500g
Protection ratingIP50

Frequently asked questions

What is the recommended calibration interval?

The recommended calibration interval is 1 year or follow the instructions on the instrument.

How do I save a measurement?

Press the Enter key to save a measurement in the temporary memory.

How do I change the measurement unit?

Press the Unit key to cycle through available units such as m/s, fpm, l/s, m3/h, and hPa.

What is the K2 factor used for?

The K2 factor compensates for friction resistance along the channel wall in ventilation channels to ensure precise flow measurements.