This document is the operation and installation manual of Delta-T Control / Energy Meter, which introduces the functions and features of the device
The EagleSun DTC-ES-1 Delta-T Control / Energy Meter is designed for use on solar thermal systems. It monitors collector and storage water temperature sensors and operates their respective water pumps to maintain the desired differential temperature. The unit features an integral variable speed drive for the collector pump and on/off control for the storage pump. It can read flow and auxiliary temperature sensors to calculate BTU and transmit data to a PC via RS-232 for logging and diagnostics.
| Line voltage | 115Vac (L, N, G), 15Amps |
|---|---|
| Collector sensor type | 10k Thermistor, 5Vdc circuit |
| Storage sensor type | 10k Thermistor, 5Vdc circuit |
| Flow sensor input | FS, GND, 5V 5Vdc circuits |
| Variable speed pump output | Phase controlled line voltage, Triac: 4Amps max |
| Fixed speed pump output | Line voltage, Relay contacts: 20A (or 2HP motor)@240VAC, NO |
| Communication interface | 5Vdc power, TX (RS-232) at 10Vdc, RJ45 jack |
| Display type | LCD type with 2x16 characters, backlit |
| Operating temperature | -32°F (0°C) to 140°F (60°C) |
Press the MENU button and hold it for 6 seconds.
BTU is calculated as FLOW (GPM) * 500 * (AUX2-AUX1).
The control will disengage the pumps to prevent the tank from overheating.
It is mounted against or adjacent to the water storage tank using two #6 screws spaced vertically 7-9/16" apart.