Albi Clad TF Fireproofing Application Manual & Field Guide

Albi Clad TF Fireproofing Application Manual & Field Guide


Albi Clad TF Fireproofing Application Manual & Field Guide - cover page
Brand
Albi
Category
Other
Document type
User Manual
Language
English
Pages
17
File format
PDF
File size
193 KB
Published
21 October, 2023
Updated
21 October, 2023
MD5 checksum
B8B1480A4327AC13876B7797627D33C1

About this manual

Albi Clad TF is a proprietary, water-based fireproofing system designed for interior application on structural steel where the finish is to remain exposed. It is a smooth, hard coating that withstands heavy service, impact, and vibration while maintaining aesthetic properties. The product is factory formulated with acrylic-based resins and intumescent agents, containing no asbestos, and meets ASTM E84, ASTM E119, and UL 263 criteria. It is available in spray and trowel grades and does not require a topcoat for performance, though it may be painted with a compatible product if desired.

What's inside

  • Introduction – Applicator Training
  • Albi Clad TF Product Description
  • Equipment Recommendations
  • Airless Spray Equipment
  • Surface Preparation
  • Primers
  • Mixing the Material
  • Airless Spray Application
  • Troubleshooting
  • Warranty/Guarantee

Specifications

Formulation TypeProprietary water based formulation consisting of acrylic-based resins, binders, and intumescent agents
Shipping Containers55-gallon (US) drums or 5-gallon (US) pails
Asbestos ContentNO asbestos
Fire Test CriteriaASTM E84, ASTM E119 and UL 263
Minimum Pump Delivery1.25 gallons per minute
Hose Working Pressure3000 + psi
Recommended Tip Sizes.419-.423 & .519-.523
Primer Cure Timeat least 72 hours
Film Thickness per Coat60 – 100 mils

Frequently asked questions

Does Albi Clad TF require a topcoat for performance?

No, it does not require a topcoat for performance, though it may be painted with a compatible product if desired.

What primers are recommended for use with Albi Clad TF?

Albi recommends Albi 487 S (Alkyd Primer) or Albi 490 W (Acrylic Primer), both of which must cure for at least 72 hours before application.

How should Albi Clad TF be mixed before application?

It must be thoroughly mechanically mixed in the field to a smooth, creamy consistency to transform its texture from heavy initial viscosity to sprayable.

What is the minimum material delivery rating for pumps used with Albi Clad TF?

Pumps must be rated for a minimum material delivery of 1.25 gallons per minute.

Download PDF (193 KB)