Albi Clad TF Fireproofing Application Manual & Field Guide
Albi Clad TF is a proprietary, water-based fireproofing system designed for interior application on structural steel where the finish is to remain exposed. It is a smooth, hard coating that withstands heavy service, impact, and vibration while maintaining aesthetic properties. The product is factory formulated with acrylic-based resins and intumescent agents, containing no asbestos, and meets ASTM E84, ASTM E119, and UL 263 criteria. It is available in spray and trowel grades and does not require a topcoat for performance, though it may be painted with a compatible product if desired.
| Formulation Type | Proprietary water based formulation consisting of acrylic-based resins, binders, and intumescent agents |
|---|---|
| Shipping Containers | 55-gallon (US) drums or 5-gallon (US) pails |
| Asbestos Content | NO asbestos |
| Fire Test Criteria | ASTM E84, ASTM E119 and UL 263 |
| Minimum Pump Delivery | 1.25 gallons per minute |
| Hose Working Pressure | 3000 + psi |
| Recommended Tip Sizes | .419-.423 & .519-.523 |
| Primer Cure Time | at least 72 hours |
| Film Thickness per Coat | 60 – 100 mils |
No, it does not require a topcoat for performance, though it may be painted with a compatible product if desired.
Albi recommends Albi 487 S (Alkyd Primer) or Albi 490 W (Acrylic Primer), both of which must cure for at least 72 hours before application.
It must be thoroughly mechanically mixed in the field to a smooth, creamy consistency to transform its texture from heavy initial viscosity to sprayable.
Pumps must be rated for a minimum material delivery of 1.25 gallons per minute.