This manual describes installation, operation, and maintenance of the HTC Series Heat Exchangers.
This manual provides step-by-step instructions for installing, operating, and maintaining VoltAire HTC Series air-to-air counter flow heat exchangers rated for 48VDC. It covers product specifications, installation procedures, wiring, controls, cutout drawings, troubleshooting, and maintenance. The units are designed for high-efficiency heat transfer in closed airflow loops, suitable for electronic enclosures and battery backup systems. They operate in extreme temperatures from -40ºF to 158ºF (-40ºC to 70ºC) and include an integrated 48VDC control board for fan speed modulation based on interior temperature.
| Nominal Capacity | 15W/ºF (27W/ºC) to 90W/ºF (162W/ºC) |
|---|---|
| Rated Voltage | 48VDC |
| Operating Temperature Range | -40ºF to 158ºF (-40ºC to 70ºC) |
| Certifications | UL 1995 and Type 4/4X |
| Fan Control | Integrated 48VDC control board modulates fan speed based on interior temperature |
The HTC Series heat exchangers are available in capacities of 15W/ºF (27W/ºC), 20W/ºF (36W/ºC), 25W/ºF (45W/ºC), 42W/ºF (75W/ºC), and 90W/ºF (162W/ºC).
The units operate in an extreme temperature range from -40ºF to 158ºF (-40ºC to 70ºC).
The units are UL/cUL Recognized per UL 1995/CSA 22.2 NO. 236-15 and UL tested and UL Recognized for compliance with UL Type 4/4X.