provides the model and function introduction of electric-pneumatic positioner
This manual provides instructions for the Clorius Controls EPR Series electro-pneumatic positioner, an industrial device used for controlling pneumatic rotary actuators. It details the part number system, specifications, and various mounting configurations including NAMUR and fork lever types.
The document guides users through the setup process, including cam and indicator adjustment, zero and span calibration, and electrical connections. It also includes troubleshooting tips for common issues such as hunting, valve sticking, and poor linearity.
| Input Signal | 4 ~ 20mA DC |
|---|---|
| Air Supply | Max. 7.0bar (100psi) |
| Standard Stroke | 60 ~ 100 ° |
| Protection Class | Ex md IIB T6, Ex md IIC(H2) T6, IP66 |
| Ambient Temperature | -20 ~ +70 °C |
| Weight | 2.9 kg (with terminal box) |
| Power Supply Rating | 5.5 ~ 30V DC loop-powered |
| Recommended Power Supply | 24V DC |
| Output Signal | 4~20mA |
| Linearity | ± 1.0 % F.S |
The standard factory setting is RA (reverse acting).
The maximum air supply pressure is 7.0 bar (100 psi).
The air filter regulator should be installed before the EPR positioner.
The recommended power supply is 24V DC.