This document is the instruction manual for fire dampers, smoke dampers and smoke valves
This manual covers fire dampers, smoke dampers, and smoke valves manufactured by Guangzhou Panyu Zhenxing Fire Equipment Co., Ltd. It details their functions, structural principles, installation, and maintenance. Fire dampers close at 70°C, smoke dampers at 280°C, and smoke valves open manually or electrically during fire or smoke evacuation. Components include valve bodies, blades, actuators, and temperature sensors. The manual also provides product classifications, control methods, and common specifications with flange dimensions.
The document includes technical parameters such as corrosion resistance, temperature sensitivity, operating voltage (DC20.4–26.4V), leakage rate, and fire resistance time (≥1.50 hours). It explains different valve types (e.g., self-weighted, regulated, remote-controlled) and their operational mechanisms, including manual and automatic closing via temperature sensors or electrical signals. This manual is written in Chinese.
| Operating Voltage | DC20.4~26.4V |
|---|---|
| Operating Current | ≤0.7A |
| Fire Resistance Time | ≥1.50 hours |
| Leakage Rate | ≤700m³/(m²·h) at 300±15Pa |
| Temperature Trigger for Fire Damper | 70°C |
| Temperature Trigger for Smoke Damper | 280°C |
| Manual Closing Force | ≤70N |
Fire dampers close when the pipe temperature reaches 70°C.
Smoke dampers close when the smoke duct temperature reaches 280°C.
The fire resistance time is not less than 1.50 hours.
The actuators operate reliably within DC20.4–26.4V.