ZP-5053 Digital Megohmmeter is widely used in power station and power plant for equipment maintenance, such as insulation resistance, absorption ratio, polarization index of high-voltage electrical equipment such as transformers, reactors, capacitors, circuit breakers.
This manual provides detailed instructions for operating the ZP-5053 high voltage digital megohmmeter, including setup, testing procedures, and safety precautions. It covers measurement of insulation resistance, absorption ratio, and polarization index for high-voltage equipment. The device features a 128x64 dot matrix display, four voltage settings (500V, 1000V, 2500V, 5000V), and automatic calculation of test parameters. Safety warnings and battery maintenance guidelines are emphasized throughout. This manual is written in Chinese.
| Output Voltage | 500V, 1000V, 2500V, 5000V |
|---|---|
| Short Circuit Current | 5mA |
| Battery Capacity | 2600mAh lithium rechargeable battery |
| Display | 128 × 64 dot matrix display with backlight |
| Dimensions | 285mm × 247mm × 120mm |
| Weight | 2200g |
| Operating Temperature | 0°C ~ 40°C |
| Relative Humidity | 20%~90%RH |
| Power Supply | DC 16.8V (2600mAh) or AC 140V~240V 50Hz |
The output voltage range is 500V, 1000V, 2500V, and 5000V.
It uses a 2600mAh lithium rechargeable battery.
The charging time is approximately 6 hours.