provides a technical manual for the maintenance and repair of wet pipe sprinkler systems
This manual provides detailed instructions for the operation, maintenance, and troubleshooting of Viking wet pipe sprinkler systems. It covers system components such as check valves, relief valves, and pressure gauges, along with installation requirements and testing procedures. The manual also includes troubleshooting sections for common issues like false alarms and pressure drops.
The system is designed for use in structures reliably maintained above 40°F (4°C) and complies with NFPA 13, FM Global, and other recognized standards. It includes diagrams and specifications for components like the Model J-1 Alarm Check Valve and Model C-1 Retard Chamber, with guidance on proper installation and maintenance intervals.
| Relief Valve Size | 1/4” (6 mm) |
|---|---|
| Relief Valve Pressure Setting | 175 PSI (12.1 bar) or 10 PSI (0.7 bar) above maximum system pressure |
| Gauge Accuracy | within 3 percent of full scale |
| Gauge Replacement Interval | every 5 years |
Up to 52,000 square feet for light and ordinary hazard; 40,000 for extra hazard - hydraulically calculated; 25,000 for extra hazard - pipe schedule.
Every 5 years, or tested every 5 years by comparison with a calibrated gauge.