This document is a BRUEST CATALYTIC HEATERS Troubleshooting Guide. It mainly introduces the usage methods and troubleshooting methods of the product.
This document provides a step-by-step guide for diagnosing issues where a Bruest catalytic heater shuts off after a few days of operation. It details procedures for checking gas pressure using specific gauges and adjusting the Baso Safety Valve and thermostatic gas valve to ensure proper flow readings.
The gauge should read 3.5" w.c. or 2 oz. to show full flow from the regulator through the orifice into the pad.
You should see a reading of 1 — 1.5" w.c. or approximately 1 oz. This indicates the thermostatic gas valve is working properly.
The reading should be 10-15 milivolts when the unit is on preheat and the probes are placed on the thermocouple and tubing.
Most Bruest Catalytic Heaters can be rebuilt at the Bruest Catalytic Heater factory in Independence, Kansas.