This manual provides information on installation, operation, maintenance etc. of L&T low voltage switchgear.
This document serves as a comprehensive guide for the L&T PCC (TS) Low Voltage Power Control Center. It details the construction features, including modular design and compliance with IEC 61439 standards, as well as technical data regarding voltage and current ratings. The manual provides step-by-step instructions for handling, transportation, storage, and installation, including site preparation and panel mounting.
| Rated operational voltage (U)e | up to 690 V |
|---|---|
| Rated insulation voltage (U)i | 1000 V |
| Rated impulse withstand voltage (U)imp | 6 / 8 / 12 kV |
| Rated frequency (f)n | 50 / 60 Hz |
| Main Horizontal busbars Rated current (I)nA | up to 6300 A |
| Main Horizontal busbars Rated peak withstand current (I)pk | up to 220 kA |
| Main Horizontal busbars Rated short-time withstand current (I)cw | up to 100 kA, 1s |
| Height | 2200, 2400 mm |
| Width | 700, 900, 1000 mm |
| Depth | 600, 1000, 1100 mm |
Only authorized and qualified personnel should be allowed to work on the switchgear.
In case of any conflict between this manual and drawings available with you, the drawings shall take precedence.
The TS range of Low Voltage Power Control Centers complies with IEC 61439-Part1 & 2.