Delta multi-technology readers quick reference guide
This guide covers the setup and operation of Farpointe Data's Delta multi-technology readers, including models Delta3, Delta5, Delta5.3, and Delta 6.4. It details cable requirements, power specifications, and credential compatibility for 13.56 MHz and 125 kHz RFID cards. The guide also explains output formats for contactless smartcards and secure sector data.
Wiring details are provided with color-coded pin assignments for connections to an access panel, including power, data, and control lines. Grounding and shielding requirements are specified to ensure proper operation.
| Cable Length | up to 500 feet (152 m) |
|---|---|
| Minimum Wire Gauge | AWG 24 |
| Operating Voltage | 5 to 14 VDC |
| Default Output Format | 32-bit Wiegand |
The guide covers Delta3, Delta5, Delta5.3, and Delta 6.4 multi-technology readers.
They can read 13.56 MHz ISO 14443 Type A/B cards and 125 kHz Pyramid, HID, or AWID proximity credentials.
The default is 32-bit Wiegand data starting with the MSB.
A separate, linear power supply is preferred, though the readers can be powered by the access panel.