Introduces the characteristics and applications of Medium Voltage Solid State Soft Starters 2.3 - 7.2 kV products, including overview, specifications, design features, principles, general protection, thermal overload protection, trigger circuit, electronics circuit, etc.
This manual provides detailed instructions for installing, operating, and programming medium voltage solid state soft starters. It covers unit specifications, control connections, startup procedures, user interface navigation, setpoint programming, metering, and maintenance. The device is an SCR-based motor controller designed for AC medium voltage motors, with programmable overload curves, phase imbalance protection, and communication options via RS-485, RS-422, or RS232.
The manual includes wiring diagrams, fault analysis, spare parts lists, and troubleshooting charts to assist with setup and maintenance. It also details programmable parameters such as acceleration/deceleration ramps, relay configurations, and RTD options for temperature monitoring.
| Unit Running Overload Capacity | 125% - Continuous, 500% - 60 seconds |
|---|---|
| Frequency | 50 or 60Hz, +2Hz hardware selectable |
| SCR Peak Inverse Voltage Ratings | 6500V - 19500V (model dependent see Table 1) |
| Control Voltage | 120VAC (customer supplied) |
| Relays | 8 Relays (4 programmable): Form C contacts |
| BIL Rating | 2300V - 7200V |
| Overcurrent Protection Trip Level | 100 - 300% of motor FLA |
| LCD Display | Alpha numeric LCD display |
| Communication Protocol | Modbus RTU |
| Network Capacity | Up to 247 devices per mode |
| Operating Memory | SRAM loaded from EEPROM at initialization |
| Factory Default Storage | Flash EPROM, field replaceable |
| Real Time Clock | Lithium ion battery for clock memory only |
The soft starter operates in the 2.3 - 7.2 kV range.
The unit can handle 125% continuous overload and up to 500% for 60 seconds.
The device supports Modbus RTU over RS-485, RS-422, or RS232.
The unit has 8 relays, with 4 programmable Form C contacts.