EG-3000 Smoke Limiting Governor Controller Operation Manual

EG3000 Smoke Limiting Governor Controller with Idle Speed Control suitable for All Type of Injection Pumps including PT Pumps, Built-in and Non Built in injection Pumps and electric over Oil Pressure Systems.


EG-3000 Smoke Limiting Governor Controller Operation Manual - cover page
Brand
EG3000
Category
Industrial Robot
Document type
User Manual
Language
English
Pages
7
File format
PDF
File size
249 KB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
0327985F7A7D7F159B2F3AFF6C6C8508

About this manual

This manual provides step-by-step instructions for installing and operating the EG-3000 Smoke Limiting Governor Controller. It covers specifications, connection diagrams, idle speed and ramp time adjustment, isochronous and non-isochronous operation, and remote speed control. The controller is designed for use with various injection pump types including PT pumps and electric over oil pressure systems.

The EG-3000 receives signals from a magnetic pickup and controls fuel intake via an actuator to maintain engine speed. It operates on 12 or 24 VDC and features adjustable parameters including run speed, idle speed, ramp time, droop, gain, and integration for optimal engine performance.

What's inside

  • Specifications
  • Function Descriptions
  • Installation Descriptions
  • Connection
  • Operation
  • Idle Speed and Smoke Limiting Adjustment
  • Isochronous Adjustment
  • Non-isokinetic Operation
  • Remote Speed POT Adjustment
  • INT, GAIN, DIF Adjustment

Specifications

Operating Voltage12 or 24 VDC ±20%
Output Current0.5 ~ 15 A
Speed Adjustment Range4 Segment Dip Switch Adjustable From 600 ~ 9500 Hz
Idle Speed Adjustment Range30 ~ 85% Run Speed
Ramp Time3 ~ 20 Sec
Temp. Stability<0.01%
Run Speed Stability± 0.25 % at steady state
Dimensions147mm L * 114mm W * 50mm H
Weight690g ± 2%

Frequently asked questions

What is the operating voltage for the EG-3000?

The operating voltage is 12 or 24 VDC ±20%.

What is the purpose of the Droop potentiometer?

The Droop potentiometer adjusts the engine speed drop under load; setting it fully counterclockwise enables isochronous operation.