TCI KRF Series 3-Phase EMC Filter Installation, Operation and Maintenance Manual

This manual introduces the use of KRF EMC 3-phase filters, including installation, operation and maintenance.


TCI KRF Series 3-Phase EMC Filter Installation, Operation and Maintenance Manual - cover page
Brand
TCi
Category
Industrial Supply
Document type
Service Manual
Language
English
Pages
52
File format
PDF
File size
4.5 MB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
D84E0EB98AF55159D2751BA645B2B843

About this manual

This document serves as the Installation, Operation, and Maintenance Manual for TCI KRF Series 3-phase EMC filters. These filters are designed to limit high-frequency noise, reduce interference, protect sensitive equipment, eliminate drive cross-talk, and meet FCC Regulation 15, Subpart J requirements. The manual covers models with voltage ratings of 520V or 760V and terminal types including Terminal Block (TB) and Copper Bus (CB), with current ratings ranging from 8A to 2500A.

The guide details safety cautions, mounting instructions, and specific procedures for different filter configurations. It emphasizes the importance of proper grounding, large-area connections, and low-inductance paths to ensure electromagnetic compatibility. Technical data, including typical circuit diagrams, test conditions, and insertion loss characteristics, are provided for various part numbers within the KRF series.

What's inside

  • Cautions and Warnings
  • Important Notes
  • Mounting Instructions
  • Part Number System
  • Technical Data
  • Insertion Loss
  • Common Mode Characteristics
  • Differential Mode Characteristics

Specifications

Rated Voltage520V or 760V
Current Rating8 to 2500 amps
Termination TypesTerminal Block (TB) or Copper Bus (CB)
Test Voltage (line/line)2236 V DC, 2 s
Test Voltage (lines/case)2720 V DC, 2 s
Climatic Category25/100/21

Frequently asked questions

What safety measures are required before installing the EMC filter?

Only qualified persons (electricity specialists) should engage in planning, assembly, installation, operation, repair, and maintenance, and they must be provided with the corresponding documentation.

When should protective earth connections be made during installation?

Protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected.

What is the recommended method for PE connections for currents greater than 250 A?

The PE connection should be set up between the feed and output not via the PE terminal bolt in the filter housing, but ideally connected to a PE busbar.

Download PDF (4.5 MB)