This manual introduces general precautions for HBC/975 gas safety cut-off device installation, start-up and maintenance, precautions for operators, handling and installation methods, maintenance recommendations and troubleshooting guide.
This service manual provides detailed instructions for installing, commissioning, and maintaining the HBC/975 gas safety cut-off device. It covers safety precautions, handling, and operational settings. The device is designed for use in systems transporting flammable gases and features adjustable pressure intervention and manual reset. Maintenance procedures and component lists are included.
The manual also addresses compliance with EU Directive 97/23/EC and standards EN 12186 and EN 12279. It includes troubleshooting and maintenance guidelines, with verification procedures for internal and external tightness. The device is suitable for medium and high pressures, with a design pressure of 100 bar and operating temperature range from -10°C to +60°C. This manual is written in Italian.
| Design Pressure | 100 bar |
|---|---|
| Operating Temperature | -10° to +60°C (-20° to +60°C on request) |
| Maximum Pressure Intervention | 1 – 85 bar |
| Minimum Pressure Intervention | 0.4 – 75 bar |
| Closing Speed Adjustment | 0.5 to 2 sec |
The design pressure is 100 bar.
The operating temperature range is from -10°C to +60°C, with an optional range of -20°C to +60°C.
The device can intervene for maximum pressure between 1 and 85 bar, and for minimum pressure between 0.4 and 75 bar.
Yes, the closing speed can be adjusted from 0.5 to 2 seconds.