This document is the operating manual of industrial pressure transmitter TKDA/TPSADA/TPFADA/TPHADA series.
This manual provides instructions for the Digital AutOzerO industrial pressure transmitter series (TKDA/TPSADA/TPFADA/TPHADA). It details the activation of additional functions such as Autozero, Fine-Autozero, Calibration, Autospan, and Reset procedures using a magnetic pen or CAL pin.
| Zero unbalancement limit (Autozero) | ± 10% FS |
|---|---|
| Zero unbalancement limit (Fine-Autozero) | ± 10% FS |
| Zero unbalancement limit (Calibration) | ± 20% FS |
| Span unbalancement limit | ± 5% of the FS |
| Autozero duration | 1 to 10 sec |
| Fine-Autozero duration | 10 to 30 sec |
| Partial Reset duration | 30 to 60 sec |
| Total Reset duration | over 60 sec |
The CAL function is activated by closing the contact between specific pins depending on the connector version (e.g., pin E-F for 6 pole, pin 5-6 for 7 pole).
The output for current transmitter series will increase around 7mA, but this is a short variation that does not affect the final result.
It is activated in three steps: 1° Autozero at 0 bar, short-circuiting the CAL pin at Full Scale (FS), and 2° Autozero at 0 bar.